Temperature Controllers:

piccolo™ Controller

piccolo™

Temperature and Process Controller

Temperature Controllers: piccolo™ Controller Temperature Controllers: piccolo™ Controller

Standards/Approvals: CE, cUL listed (file ES7766)

Standards/Approvals: cUL listed (file ES7766) Standards/Approvals: cUL listed (file ES7766)
Standards/Approvals: CE Standards/Approvals: CE

P116 Dimensions -

General views of the controllers are shown below together with overall dimensions.

piccolo™ Controller - P116 Dimensions piccolo™ Controller - P116 Dimensions
piccolo™ Controller - P116 Dimensions piccolo™ Controller - P116 Dimensions

P116 Rear Terminals -

piccolo™ Controller - P116 Rear Terminals piccolo™ Controller - P116 Rear Terminals
piccolo™ Controller - P116 Rear Terminals piccolo™ Controller - P116 Rear Terminals

Eurotherm piccolo™ controllers offer precision PID control of temperature and other processes with many advanced features not normally found in this class of controllers.

Designed to offer outstanding performance in an affordable package providing a complete solution for a wide variety of applications, this range guarantees extremely easy access to
parameterization and operation in a high quality unit.

Despite their advanced features, the controllers are easy to use and apply and may be customized for ease of operation. Full autotune is provided.

 

High quality and high reliabilty

The piccolo controller is a high quality and high reliability
unit from a world leading manufacturer with global
support and service facilities. A 3 year warranty is pro-
vided as standard.

Ramp-soak timer and soft start

A ramp soak timer is provided for time based profiling
of temperature sequences. These can be used to
gradually vary the temperature in a control zone before
maintaining it at a defined level, and is typically used to
avoid the dangers of damage due to thermal shock.

Energy usage estimation

The piccolo controller allows estimation of energy
usage to provide basic data for evaluating energy
saving control strategies for continuous improve-
ment and Kaizen techniques.

Overshoot elimination

The Eurotherm unique cutback system ensures pre-
cise control to setpoint and when correctly tuned
inhibits temperature overshoot.

Real-World Application

  • Plastic Processing Control 

    The precision PID controller is used to ensure
    uniform heating of the material to avoid material
    derogation, undue strain on the extruder
    components and improve process reliability.

    Can be used to consolidate functions and replace
    several interconnected devices to chillers, including
    an external timer.
  • Incubators

  • Food and Beverage

    The simple timer may be used to control
    batch operations, e.g., food ovens, fryers
    and sterilizers.
  • Furnaces, Ovens & Kilns

    Well adapted for firing ceramics and heat
    treating complex parts.
  • Laboratory Equipment

Environmental Performance  
Temperature Limits Operation: 0 to 60°C
Storage: -10 to 70°C
Humidity Limits Operation: 0 to 90% RH non condensing
Storage: 5 to 90% RH non condensing
Panel Sealing: IP65
Shock: BS EN61010
Vibration: 2g peak, 10 to 150Hz
Altitude: < 2000 meters
Atmospheres: Not suitable for use in explosive or corrosive atmosphere
Electromagnetic Compatibility (EMC)
Emissions and Immunity: BS EN61326
Electrical Safety  
(BS EN61010): Installation cat. II; Pollution degree 2
INSTALLATION CATEGORY II The rate impulse voltage for equipment on nominal 230V mains is 2500V
POLLUTION DEGREE 2 Normally, only non-conductive pollution occurs. Occasionally however, a temporary conductivity caused by condensation shall be expected.
Physical  
Panel Mounting: 1/16 DIN
Weight: 250g
Panel Cut-Out Dimensions: 45mm W x 45mm H
Panel Depth: 90mm
Operator Interface  
Type: LED
Main PV Display: 4 digits, green
Secondary Display: 4 digits, amber
Status Beacons: Units, outputs, alarms, active setpoint
Power Requirements 100 to 230 ±15%
48 to 62 Hz, max 6W
24V ac, -15%, +10%
24V dc, -15% + 20% ±5% ripple voltage
Max 6W
Approvals CE, cUL listed (File ES7766)
Suitable for use in Nadcap and AMS2750E applications under Systems Accuracy Test calibration conditions
Other standards pending
Process Variable Input  
Calibration Accuracy: <±0.25% of reading ±1LSD
Quoted over full ambient operating range and for all input linearisation types
Sample Rate: 4 Hz (250ms)
Resolution (µV): <0.5µV with 1.6sec filter
Resolution (effective bits): >17 bits
Linearisation Accuracy: <0.1% of reading
Drift with Temperature: <50ppm (typical) <100ppm (worst case)
Common Mode Rejection: 48-62 Hz, >-120dB
Series Mode Rejection: 48-62 Hz, >-93dB
Input Impedance: 100MΩ
Cold Junction Compensation: >30:1 rejection of ambient change
Cold Junction Compensation: >30:1 rejection of ambient change
Cold Junction Compensation: >30:1 rejection of ambient change
Cold Junction Accuracy: <±1°C at 25°C ambient
Linear (process) Input Range: -10 to 80mV, 0 to 10V with 100K/806 external divider module
Thermocouple Types: K, J, N, R, S, B, L, T, C
Resistance Thermometer Types: 3-wire Pt100 DIN 43760
Bulb Current: 0.2mA
Lead Compensation: No error for 22 ohms in all leads
Input Filter: Off to 59.9s
Zero Offset: User adjustable over full range
User Calibration: 2-point gain & offset
OP 4 Relay  
Type: Form C (changeover)
Rating: Min 100mA @ 12V dc, max 2A @ 264V ac resistive
Functions: Control outputs, alarms, events
Logic Output Module  
Rating: ON 12V dc @ <44mA; OFF <300mV @ 100µA
Isolation: None from PV or system, 264V ac double insulated from PSU and communications
Functions: Control outputs, alarms, events
Relay Output Channels  
Type: Form A (normally open)
Rating: Min 100mA @ 12V dc, max 2A @ 264V ac resistive
Functions: Control outputs, alarms, events
Analogue Output - OP2 Voltage output can be achieved by external adaptor
Rating: 0-20mA into <500Ω
Accuracy: ±(<1% of Reading + <100µA)
Resolution: 13.5 bits
Isolation: 264V ac double insulated from PSU and communications
Functions: Control outputs, retransmission
Software Features - Control  
Number of Loops: 1
Loop Update: 250ms
Control Types: PID, ON/OFF
Cooling Types: Linear, fan, oil, water
Modes: Auto, manual, standby
Overshoot Inhibition: High, low
Software Features - Alarms  
Number: 3
Type: Absolute high & low, deviation high, low or band
Latching: Auto or manual latching, non-latching
Output Assignment: Relay and digital output
Other Status Outputs - Functions: Including sensor break, timer status, loop break, heater diagnostics
Timer - Modes: Dwell when setpoint reached; Delayed control action, Soft start limits power below PV threshold
Current Monitor - Alarm Types: Over current, SSR short circuit, SSR open circuit
Current Monitor - Indication Type: Flashing Beacon
Special Features: Energy monitoring, recovery point
INDUSTRY-NET-PREFERRED-SUPPLIER-LOGO
  • Calculator
  • Standard Flow Rate (SCFM) Calculator

    Calculate the SCFM.

    Power Flowrate Calculator

    Calculate the electrical power, flow rate or temperature requirement.

    Temperature Conversion

    Fill in one value to calculate the other.

    Ohms Law Calculator

    Fill in two values to find the other two.

    Pressure Conversion

    Fill in one value to calculate the other.

    Three Phase Unit Calculator

    Fill in two values to find the 3rd.

    Single Phase Unit Calculator

    Fill in two values to find the 3rd.

    Parallel Resistance Calculator

    Calculate the total resistance in ohms of resistors that are in parallel by entering the value of each below.

    Series Resistance Calculator

    Calculate the resistance in ohms of resistors connected in series by entering the value of each.

    Copyright © 2024 Convectronics. All Rights Reserved.