JCL-33 Standard Specifications Convectronics Manufactures First Class Heaters, Temperature Sensors and Precise Controls, Assists with Design and Application Needs.

HEATERS   SENSORS   CONTROLS

Convectronics Phase Angle Control Consoles
ACS-13A Digital Indicating Controller
JCL-33 Digital Indicating Controller with Ramp/Soak
Standard Specifications
Diagrams/Schematics
Product Configurator
JC Series Digital Indicating Controllers
FPT Series Single-Phase Power Controllers

Controllers
JCL-33 Standard Specifications

 
Model JCL:
1/32 DIN (48mm X 24mm)
     
     
Input Range Table
   
Input Type Input Range
Thermocouple K -200 to 1370°C -320 to 2500°F
  -199.9 to 400.0°C -199.9 to 750.0°F
J -200 to 1000°C -320 to 1800°F
R 0 to 1760°C 0 to 3200°F
S 0 to 1760°C 0 to 3200°F
B 0 to 1820°C 0 to 3300°F
E -200 to 800°C -320 to 1500°F
T -199.9 to 400.0°C -199.9 to 750.0°F
N -200 to 1300°C -320 to 2300°F
PL-II 0 to 1390°C 0 to 2500°F
C (W/Re 5-26) 0 to 2315°C 0 to 4200°F
RTD Pt100 -200 to 850°C
-199.9 to 850°C
-300 to 1500°F
-199.0 to 999.9°F
JPt100 -200 to 500°C
-199.9 to 500.0°C
-300 to 900°F
-199.9 to 900.0°F
DC Current 4 to 20mA DC
0 to 20mA DC
 
DC Voltage 0 to 1V DC
0 to 10V DC
1 to 5V DC
0 to 5V DC
-1999 to 9999*
-19.99 to 99.99*
-199.9 to 999.9
- 1.999 to 9.999
*For DC current and DC voltage inputs, scaling and decimal point place are changeable.
*For DC current input, 50Ω shunt register (sold separately) must be installed.
   
> To Top    
     
Standard Specifications
 
Display Display PV/SV Red Digits 8.7 (H) x 5(W)mm
Input Thermocouple K, J, R, S, B, E, T, N, PL-II, C (W/Re5-26) External resistance: 100Ω or less(However, for B input: 40Ω or less)
RTD Pt100, 3-wire system
(Allowable input wire resistance per wire: 10Ω or less)
DC current 0 to 20mA DC,
4 to 20mA DC
Input impedence: 50Ω
(Connect shunt resistor 50Ω between input terminals)
Allowable input current: 50mA DC or less
(When shunt resistor 50Ω is used)
DC voltage 0 to 1V DC Input impedence: 1MΩ or greater
Allowable input voltage: 5V DC or less
Allowable signal source resistance: 2kΩ or less
0 to 5V DC,
1 to 5V DC,
0 to 10V DC
Input impedence: 100kΩ or greater
Allowable input voltage: 15V DC or less
Allowable signal source resistance: 100Ω or less
Accuracy
(Setting - Indicating)
Thermocouple Within +/-0.2% of each input span +/-1 digit or +/-2°C (4°F), whichever is greater
However, R or S input 0 to 200°C (0 to 400°F): Within +/-6°C (12°F)
B input 0 to 300°C (0 to 600°F): Accuracy is not guaranteed
K, J, E, and N input less than 0°C (32°F): Within +/-0.4% of input span +/-1 digit
RTD Within +/-0.1% of each input span +/-1 digit or +/-1°C (2°F), whichever is greater
DC current and
DC voltage
Within +/-0.2% of each input span +/-1 digit
Input Sampling
Period
0.25 seconds
Control Output
(OUT 1)
Relay contact 1a, 3A 250V AC (Resistive load), 1A 250V AC (Inductive load cos φ=0.4). Electric life: 100,000 times
Non-contact DC voltage 12-14V DC Max. 40 mA (short-circuit protected)
DC current 4 to 20mA DC Load resistance: Max. 550Ω
Control Action Actions mentioned below can be selected by key operation (Factory default set as PID)
PID (with auto-tuning function), PI, PD (with manual reset function), P (with manual reset function), ON/OFF
OUT Proportional band (P) 0.0 to 110% (ON/OFF action when set to 0)
Integral time (I) 0 to 1000 seconds (OFF when set to 0)
Derivative time (D) 0 to 300 seconds (OFF when set to 0)
OUT Proportional cycle 1 to 120 seconds (Not available for DC current output type)
ARW 0 to 100%
Hysteresis Thermocouple and RTD: 0.1 to 100.0°C (°F)
DC current and DC voltage: 1 to 1000 (Decimal point place follows the selection)
Event Output 1
(EV1)
Event Output 2
(EV2)
Alarm action, Timer function and Pattern end function can be selected by keypad. For the inputs with a decimal point, the negative minimum value is -199.9 and the positive maximum value is 999.9
Setting accuracy The same as the indicating accuracy
Action ON/OFF action
Hysteresis Thermocouple and RTD: 0.1 to 100°C (°F)
DC current and DC voltage: 1 to 1000 (Decimal point place follows the selection)
EV1 Relay contact 1a, Control capacity: 3A 250V AC (Resistive load), 1A 250V AC
(Inductive load cos φ=0.4), Electric life: 100,000 times
EV2 Open collector. Control capacity: 0.1A 24V DC (Max.)
Alarm action delayed timer function Alarm action is delayed by this function. If input enters alarm output range and
the set time has passed, the output is turned on
Alarm output hold function Once the alarm is activated, the alarm output is maintained until power is turned off
DI (Digital Input) DI input has 3 functions as shown below. Each function can be selected by keypad
• Timer Function If input signal enters from outside, timer measurement starts, and ON delay timer, OFF delay timer or ON/OFF delay timer action output is turned on after delay timer setting has passed.
• SV1/SV2 external selection function SV1 (Main setting 1), and SV2 (Main setting 2) can be selected by external contact signal. (If the JCL-33A is used as a programmable controller, this function is not available).
• OUT/OFF (RUN/STOP) external selection function: Control output OUT/OFF (Fixed value control) or Program control RUN/STOP can be switched [Fixed value control]
(If the JCL-33A is used as a programmable controller, OUT/OFF external selection function is not available) [Program control]
Program control RUN/STOP can be switched by external contact pulse input (ON time, approx. 30ms)
Simplified
Programmable
Controller Function
JCL-33A can perform 1 pattern and 9 steps of simplified program control
Progressive time error Within +/-1 minute
Pattern end output Pattern end output can be selected by front keypad
Converter Function JCL-33A has a converter function which can be easily used by changing with keypad
(However, this is available only for the DC current output type)
Mounting Method Provided with one piece mounting bracket
Setting Method Sheet key input
Material - Color Material: Flame resistant resin Color: Black
Supply Voltage 100 to 240V AC 50/60Hz, 24V AC/DC 50/60Hz
Allowable voltage fluctuation: 85 to 264V AC, 20 to 28 AC/DC, Power consumption approximately 6VA
Environment Ambient temperature: -10 to 50°C Ambient humidity: 35 to 85% RH (No condensation)
         
> To Top        
         
Options * Please specify options according to user’s needs. When ordering, specify an option code to be applied.
         
Heating/Cooling
Control
[DR]
If this option is added, Event output 1 cannot be used
Heating control action: The same as the control output (OUT)
Cooling control action:
Proportional band (P) 0.0 to 10.0 times the control output (OUT) (ON/OFF action when set to 0.0)
Integral time (I) The same as that of the control output (OUT)
Derivative time (D) The same as that of the control output (OUT)
Proportional cycle 1 to 120 seconds (Not available for DC current output type)
Overlap/Dead band Thermocouple and RTD: -100.0 to 100.0°C (°F)
DC current and DC voltage: -1000 to 1000 (Decimal point follows this selection)
Hysteresis Thermocouple and RTD: 0.1 to 100.0°C (°F)
DC current and DC voltage: 1 to 1000 (Decimal point follows this selection)
Control output (EV1) Relay contact 1a, Control capacity: 3A 250V AC (Resistive load), 1A 250V AC (Inductive load cos φ=0.4), Electric life: 100,000 times
Serial Communication
[C5]
Performs operations such as various setting status changes, setting value reading and setting, etc., from the external computer. Shinko programmable controller which has the SVTC option can digitally transmit its SV to JCL-33A units which have the C5 option
Communication interface Based on EIA RS-485
Communication speed 2400/4800/9600/19200bps (can be selected by keypad)
Communication protocol Shinko/Modbus RTU/Modbus ASCII (can be selected by keypad)
Number of connectable units A maximum of 31 units per host computer
 